FVA-R
Electronic rectangular flow regulator
Description
Electronic rectangular flow regulator for VAV/CAV applications. “Pressure independent” electronic regulation, with measurement of the instantaneous flow rate by means of a speed probe and differential pressure transducer. Control signal 0-10 Vdc (or 2-10 Vdc) proportional. Possibility of forcing the state of the regulator by means of mandatory commands: "all open", "all closed", "maximum flow", "minimum flow". Flow monitor function for viewing the instantaneous value remotely. Master-slave function for overpressure/depression control applications (models BP1 or BP2). Damper with silicone gasket along the fins (class 4/C sealing according to EN 1751). Can be used for both supply and return, placing the measuring ring (pressure probe) upstream from the damper. Regulation with Belimo (FVA-RB▢) or Siemens (FVA-RS▢) motor.
Available executions
- FVA-R ▢: standard execution
- FVA-RI ▢: like FVA-R ▢ but with with insulating cap applied externally, to attenuate the radiated noise
- FVA-R▢ spec.013: stainless steel execution
▢ = type of engine (see code in the table)
Code | Belimo | Code | Siemens |
---|---|---|---|
B1 | LMV D3 MP | S1 | GDB.181.1E |
B2 | NMV D3 MP | S2 | GLB.181.1E |
B3 | LMV D3 MOD | S3 | GDB.181.1E/KN |
B4 | NMV D3 MOD | S4 | GLB.181.1E/KN |
B5 | LMV D3 LON | S5 | GDB.181.1E/BA |
B6 | NMV D3 LON | S6 | GLB.181.1E/BA |
BP1 | NMQ 24A SR + VFP100 + VRP-M (fast running) | ||
BP2 | NM 24AV + VRP-STP + VFP100 |
Accessories
- SIL-FVA-R: rectangular silencer for FVA
- BA-FVA 2R: 2-row post-heating (water) coil